JY ZT-25/200A Loadbreak Elbow Connector

Scope of Delivery Elbow connector, test point cap, grounding wire Loadbreak probe Probe installation tool Clearing paper Silicone lubricant Conductor cable lug Installation instruction sheet Quality certificate

Share to:

General

25kV 200A Loadbreak Elbow Connector is a fully-shielded and insulated plug-in termination for connecting underground cable to distribution power system ofpad-mound transformer, surrounding power supply branch box, cable branch boxequipped with loadbreak bushings. The elbow connector and bushing insert comprisethe essential components of all loadbreak connections. It can meet the demandof lines in nuclear.
The Loadbreak Elbows are molded using high quality sulfur-cured inshulation and semi-conducting EPDM rubber. Standard features include a coppertop connector. tin-plated copper loadbreak probe with an ablative arc-follower tip and stainless steel reinforced pulling-eye. An optional capacitive test point, made of corrosion resistant plastic. is available for Use with fault indicators. The available conductor cross section is 25-150mm for 25kV cable. The conductive pole W/ARC extinguishes function.

25kV Order Information

Product Information

General

Key source specifications include Rated Voltage (Ue): 25kV(Applicable 24kV System, Maximum Operating Voltage 24kV); Rated Current (Ie): 200A; Power-Frequency Withstand Voltage: 65kV/5min(Dry Test) / 55kV/5min(Wet Test), No Breakdown / No Flashover; Lightning Impulse Withstand Voltage: 125kV(Peak), No Breakdown / No Flashover.

Features

Ethylene propylene diene monomer (EPDM) rubber insulation is employed to form a fully insulated, weather-resistant cable accessory structure.

A fully insulated and sealed design is identified for safer operation in medium-voltage distribution equipment.

Loadbreak and energized plug-in/pull-out capability are listed where the matched product specification supports switching operation.

Partial-discharge performance is included in the source specification to support long-term insulation reliability.

Waterproof and dust-resistant protection is specified for harsh indoor or outdoor cable-system environments.

Voltage sensing or live-indication capability is included for switchgear monitoring and safety indication.

Application

This 25kV cable accessory is intended for medium-voltage cable connection in ring main units, transformer cable boxes, cable branch boxes, switchgear, and related distribution equipment.

Product Images

JY ZT-25/200A Loadbreak Elbow Connector source image 1
JY ZT-25/200A Loadbreak Elbow Connector source image 1

Technical Parameters

Parameter CategoryItemTechnical Specification
Rated Electrical ParametersRated Voltage (Ue)25kV(Applicable 24kV System, Maximum Operating Voltage 24kV)
Rated Current (Ie)200A
Rated Frequency (fn)50Hz/60Hz
Power-Frequency Withstand Voltage65kV/5min(Dry Test) / 55kV/5min(Wet Test), No Breakdown / No Flashover
Lightning Impulse Withstand Voltage125kV(Peak), No Breakdown / No Flashover
Partial Discharge≤10pC(1.5U0at)
Rated Loadbreak Current200A( ≥100
Rated Short-Circuit Withstand Current16kA/2s(Selectable 20kA/2s, Cable
Contact Resistance≤100μΩ
Structural and Material ParametersMain MaterialEPDM EPDM Rubber(Insulation ) / Tin-Plated Copper
Protection DegreeIP67
CableCross-Section25~240mm2( / InsulationCable, Customizable
Interface Standard24kV Standard
Grounding MethodYellow-GreenGroundingLead Wire, Direct Grounding
Environmental ParametersApplicable Altitude≤2000m(High-Altitude Version Customizable)
Ambient Temperature-40°C to +90°C(Operating Temperature), -40°C to +70°C(Storage Temperature)
Relative Humidity≤100%(Non-Condensing)
Seismic Grade8 Class
Applicable StandardIEEE 386 / GB/T 12706 / DL/T 404 / GB/T 11022

Model Code Description

Model CodeMeaning
JYProduct Series Code
ZTLoadbreak Elbow Connector
25RatedVoltageClass, 24kV System, Maximum Operating Voltage 24kV
200ARatedCurrentClass, RatedLoadbreakCurrent 200A
Loadbreak Elbow ConnectorLoadbreak Loadbreak Elbow Connector, Energized Plug-In / Pull-Out

Order information

Before ordering, confirm interface standard, protection degree, and the required quantity according to the project drawings and source specification.

Scroll to Top