Surge Arrester Parameters
| Usage Place | Arrester Model | Rated Voltage (kV) Eff. | System Nominal Voltage (kV) RMS | Continuous Operating Voltage (kV) RMS | DC Ref. Voltage (U1mA) kV (≥) | Max Residual Voltage kV (Peak) – Surge Current | Max Residual Voltage kV (Peak) – Lightning Impulse | Max Residual Voltage kV (Peak) – Operating Impulse | 200μs Wave Current A (Peak) | 4/10μs Impulse Current A (Peak) | Max Leakage Current at 0.75 DC Ref. Voltage μA |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Capacitor | HY0.1W-14R | 1.4 | 1.4 | 1.20 | 2.6 | 9.45 | 6.85 | 3.85 | 250 | 40 | 50 |