Surge Arrester Parameters
| Tempat Penggunaan | Model Penangkal | Tegangan Terukur (kV) Nilai Efektif | Tegangan Nominal Sistem (kV) RMS | Tegangan Operasi Berkelanjutan (kV) RMS | Tegangan Referensi DC (U1mA) kV (Tidak Kurang Dari) | Tegangan Sisa Maksimum kV (Puncak) – Arus Lonjakan | Tegangan Sisa Maksimum kV (Puncak) – Impuls Petir | Tegangan Sisa Maksimum kV (Puncak) – Impuls Operasi | Arus Gelombang 200μs (Puncak) | Arus Impuls 4/10μs A (Puncak) | Arus Kebocoran Maksimum pada Tegangan Referensi DC 0,75 μA |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Distribusi (S) | HY5WZ-42/134 | 42 | 35 | 23 | 73 | 154 | 134 | 114 | 150 | 65 | 50 |
| Distribusi (S) | HY5WZ-51/134 | 51 | 35 | 40.8 | 73 | 154 | 134 | 114 | 150 | 65 | 50 |
| Distribusi (S) | HY5WZ-52,7/134 | 52.7 | 35 | 40.8 | 73 | 154 | 134 | 114 | 150 | 65 | 50 |
| Distribusi (S) | HY5WZ-54/134 | 54 | 35 | 40 | 73 | 154 | 134 | 114 | 150 | 65 | 50 |