Surge Arrester Parameters
| Tempat Penggunaan | Model Penangkal | Tegangan Terukur (kV) Ef. | Tegangan Nominal Sistem (kV) RMS | Tegangan Operasi Berkelanjutan (kV) RMS | Tegangan Referensi DC (U1mA) kV (≥) | Tegangan Sisa Maksimum kV (Puncak) – Arus Lonjakan | Tegangan Sisa Maksimum kV (Puncak) – Impuls Petir | Tegangan Sisa Maksimum kV (Puncak) – Impuls Operasi | Arus Gelombang 200μs (Puncak) | Arus Impuls 4/10μs A (Puncak) | Arus Kebocoran Maksimum pada 0,75 V Referensi DC μA |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Tegangan Rendah | HY5WZ-12,7/45 | 12.7 | 10 | 6.7 | 24 | 51.8 | 45 | 38.3 | 150 | 40 | 50 |
| Tegangan Rendah | HY5WZ-16,5/45 | 16.5 | 10 | 12.7 | 24 | 51.8 | 45 | 38.3 | 150 | 40 | 50 |
| Tegangan Rendah | HY5WZ-17/450 | 17 | 10 | 13.6 | 24 | 51.8 | 45 | 38.3 | 150 | 40 | 50 |