产品概述
TG3-24Q/175×255×310 穿墙套管 这是一种用于额定电压为 24 千伏及以下的配电系统的室内环氧树脂绝缘穿墙套管。
采用APG压力凝胶工艺一体化制造,用于高压导电母线穿过处。 switchgear 隔板、墙壁或其他接地结构。该产品提供电气绝缘、机械支撑和过渡汇流排连接。
It is widely used in 24 kV withdrawable switchgear, ring main units, and other complete power distribution equipment.
模型描述
| 型号代码 | 描述 |
|---|---|
| TG3 | Epoxy resin wall bushing series for withdrawable switchgear |
| 24Q | Rated voltage of 24 kV; Q indicates a fully insulated or reinforced insulation structure |
| 175×255 | Inner opening dimensions for the busbar: 255 mm long and 175 mm wide, with an oval or rectangular opening |
| 310 | Overall bushing height, including the upper and lower sheds, 310 mm |
产品特点
卓越的电气性能
- Manufactured from high-purity epoxy resin with high dielectric strength and low dielectric loss.
- Capable of withstanding the long-term operating voltage of a 24 kV system, as well as lightning impulse and power-frequency withstand voltage tests.
- The optimized shed structure increases the creepage distance and improves resistance to pollution flashover and moisture.
- Suitable for humid, dusty, and other demanding indoor environments.
- The fully insulated structure helps minimize partial discharge risks and supports safe and stable system operation.
可靠的机械性能
- The one-piece moulded structure provides high mechanical strength, impact resistance, and ageing resistance.
- Capable of withstanding busbar installation stress and vibration generated by the switchgear.
- The central square flange provides accurate installation positioning and reliable sealing.
- Effectively separates the internal and external spaces of the switchgear compartment.
- Lightweight construction with no risk of porcelain bushing explosion, helping improve equipment safety.
Reliable Manufacturing and Environmental Adaptability
- Manufactured using the APG pressure gelation process, providing a dense, uniform structure with no bubbles or cracks.
- High product consistency supports reliable batch installation and replacement.
- Flame-retardant performance complies with UL94 V-0.
- Resistant to high and low temperatures, chemical corrosion, and long-term ageing.
- Maintenance-free design requires only periodic cleaning of surface contamination.
技术规格
| 参数 | 规格 |
|---|---|
| 额定电压 | 24 kV, suitable for 10–35 kV three-phase AC systems |
| 额定频率 | 50/60 Hz; suitable for systems from 15 to 60 Hz |
| 额定电流 | Suitable for 630–2,500 A busbar systems, depending on busbar specifications |
| 工频耐压 | Dry test: 65 kV for 1 minute; wet test: 50 kV for 1 minute |
| 雷电冲击耐受电压 | 125 kV peak |
| 爬电距离 | ≥630 mm, meeting the insulation requirements of 24 kV systems |
| Inner Opening Dimensions | 175 × 255 mm, oval or rectangular |
| 总高度 | 310 毫米 |
| 法兰尺寸 | Suitable for standard mounting holes in 24 kV withdrawable switchgear; customizable |
| 材料 | Epoxy resin with a red insulating housing |
| 工作温度范围 | -40°C to +120°C for long-term operation |
| 阻燃等级 | UL94 V-0 |
| 适用标准 | GB/T 12944.1–12944.2 and IEC 60137 |
应用
Typical Applications
- 24 kV indoor metal-clad withdrawable switchgear, including KYN28A-24 models.
- Ring main units, box-type substations, and busbar wall-passage insulation in distribution stations.
- Power stations and substations where live conductors pass through partitions or walls.
- Insulating support for conductive components in medium-voltage distribution equipment.
- Medium-voltage distribution systems in photovoltaic and wind power booster stations.
兼容母线
The 175 × 255 mm inner opening is suitable for corresponding rectangular copper or aluminium busbars and can meet high-current transmission requirements.
操作条件
正常运行条件
- Ambient temperature: -40°C to +40°C.
- Daily average temperature: no more than +35°C.
- Installation altitude: no more than 1,000 m.
- Customized high-altitude versions are available for installations from 1,000 to 4,000 m.
- Daily average relative humidity: no more than 95%.
- Monthly average relative humidity: no more than 90%.
- Indoor installation only.
- The operating environment should be free from severe pollution, corrosive gases, and flammable or explosive substances.
- Seismic intensity should not exceed Level 8.
- Severe vibration and mechanical impact should be avoided.
Special Operating Conditions
Customized products are required for:
- High-altitude environments.
- Heavily polluted or high-salt-spray environments.
- Extremely high or low temperatures.
- Special mounting dimensions.
- Configurations requiring an integrated shielding layer.
安装与维护
安装要求
- Inspect the bushing before installation. Confirm that the surface is free from cracks, bubbles, mechanical damage, moisture, and contamination.
- Pass the busbar through the inner opening. Ensure that the busbar does not contact or press against the inner wall and that sufficient insulation clearance is maintained.
- Fit the flange closely against the switchgear partition and tighten the bolts evenly. Avoid localized stress that may cause cracking.
- After installation, inspect the insulation between the bushing and the switchgear enclosure and confirm that the grounding connection is reliable.
维护要求
- Routine inspection: Check the surface for contamination, discharge marks, cracks, and damage. Confirm that the flange seal remains intact.
- Periodic cleaning: Clean the surface using a dry, soft cloth or anhydrous alcohol. Do not use corrosive cleaning agents.
- Preventive testing: Conduct insulation resistance and withstand voltage tests regularly in accordance with applicable electrical maintenance procedures.
注意事项
- Do not operate the bushing if it is damaged, damp, or severely contaminated.
- Avoid striking or colliding with the bushing during installation to prevent damage to the insulating structure.
- The bushing is intended for indoor use only and must not be installed directly in exposed outdoor environments.
- Confirm the busbar dimensions and switchgear mounting-hole positions before selecting the product to avoid mismatching.
- Protect the product from compression, moisture, high temperatures, and direct sunlight during transportation and storage.
定制与服务
- Special dimensions, integrated shielding layers, high-altitude configurations, and other non-standard products can be customized according to project requirements.
- 提供技术支持、安装指导及售后保修服务。