WB-35Q/140 3AVS 弯曲板(安装支架)

The WB-35Q/140 3AVS Insulating Bending Plate is an insulating support component specially designed for 35 kV high-voltage switchgear, particularly 1.2-metre switchgear configurations.

分享至:

产品概述

WB-35Q/140 3AVS 绝缘弯曲板 是一种专为35千伏高压开关设备设计的绝缘支撑部件,特别适用于1.2米开关设备配置。

It is mainly installed in the busbar compartment and contact box area to provide electrical insulation and mechanical support, helping maintain the required electrical clearances and stable operation of the high-voltage circuit.

该产品通过一体化环氧树脂浇注工艺制造,提供可靠的电气绝缘和机械强度。它是 35 千伏电压等级中关键的绝缘附件之一。 switchgear 组件

技术规格

参数规格
模型WB-35Q/140 3AVS
额定电压35千伏
兼容开关设备1.2-metre high-voltage switchgear, including KYN61 and similar 35 kV cabinet types
材料Epoxy resin manufactured by APG casting
ColourRed insulating protective colour
电气间隙Meets the safety clearance requirements of 35 kV systems, ≥300 mm
绝缘电阻≥1,000 MΩ under normal room-temperature conditions
工频耐压95 kV for 1 minute, phase-to-earth
雷电冲击耐受电压185 kV peak, phase-to-earth
机械强度Designed to withstand the internal electrodynamic forces generated by switchgear short-circuit conditions
阻燃等级UL94 V-0
Protection LevelMatches the switchgear enclosure, typically IP3X or IP4X

产品特点

High Electrical Insulation Performance

The product is manufactured using an integrated epoxy resin casting process. Its smooth, uniform surface helps minimize bubbles, voids, and insulation defects.

The high dielectric strength effectively separates live conductors from grounded components, helping reduce the risk of electrical tracking, flashover, and short circuits.

Accurate Compatibility with 1.2-Metre Switchgear

The structure and mounting positions are optimized for 1.2-metre 35 kV switchgear.

The preformed mounting holes correspond with compatible cabinet structures, allowing the product to be installed or replaced without additional drilling or machining.

Reliable Mechanical Stability

The L-shaped support structure provides good resistance to bending, impact, and deformation.

It can withstand short-circuit electrodynamic forces and the mechanical stresses generated during long-term switchgear operation, helping maintain the position and stability of busbars, contact boxes, and other internal components.

Resistance to Environmental Conditions

The epoxy resin material offers good resistance to high and low temperatures, moisture, ageing, and chemical corrosion.

It is suitable for indoor substations, industrial plants, transport power systems, and other demanding indoor electrical environments.

Improved Operational Safety

The red surface makes the insulating component easy to identify during installation, inspection, and maintenance.

Rounded edges help reduce the risk of accidental scratches and handling injuries while supporting compliance with electrical equipment safety requirements.

Long Service Life and Low Maintenance

The selected insulating material offers reliable resistance to ageing, cracking, and long-term electrical stress.

Under normal operating conditions, the product can provide a service life compatible with the switchgear assembly, with minimal routine maintenance requirements.

应用

The WB-35Q/140 3AVS Insulating Bending Plate is suitable for:

  • Busbar compartments of 35 kV indoor high-voltage switchgear
  • Contact box areas in 35 kV switchgear
  • KYN61-40.5 switchgear and similar 1.2-metre cabinet configurations
  • Insulating support for busbars and other live conductors
  • Electrical clearance compensation inside switchgear
  • Mechanical fixing and positioning of contact boxes
  • Electric field distribution optimization
  • Compatible ABB-type and other mainstream 35 kV switchgear configurations
  • Urban substations
  • Industrial and mining power systems
  • Rail transit power distribution systems
  • Renewable energy power stations
  • Other 35 kV power distribution applications

操作条件

环境条件

ConditionRequirement
环境温度-40°C 至 +85°C
Short-Term Temperature ResistanceUp to +120°C
相对湿度≤95% at 25°C
Installation Altitude≤3,000 m
安装位置Indoor
冷凝Not permitted
Corrosive GasesNot permitted
Severe Vibration or ImpactNot permitted
Flammable or Explosive MediaNot permitted

For installations above 3,000 metres, equipment derating, insulation coordination adjustment, or a customized product configuration may be required.

电气状况

参数Requirement
额定系统电压35千伏
额定频率50 赫兹
Short-Time Withstand Current25–40 kA, depending on the switchgear rating
Peak Withstand Current65–100 kA, depending on the switchgear rating

The product must be used within the specified voltage and current parameters of the complete switchgear assembly.

安装要求

Before installation, clean the mounting surface inside the switchgear. Remove oil, dust, moisture, metal particles, and other contaminants.

Install the product using suitable bolts and tighten them according to the switchgear assembly specifications.

The fastening force must be applied evenly. Excessive or uneven tightening may produce installation stress and cause cracking or deformation of the insulating component.

After installation, inspect the electrical clearance between the bending plate, live components, grounded parts, and the switchgear enclosure. Confirm that all clearances meet the applicable requirements for a 35 kV system.

The product must not be installed, removed, or adjusted while the equipment is energized. All work must be completed according to the required power isolation, grounding, and high-voltage safety procedures.

Inspection and Maintenance

The product requires minimal routine maintenance under normal operating conditions. However, its condition should be inspected during scheduled switchgear maintenance.

Inspection items include:

  • Surface cracks
  • Mechanical damage
  • Electrical tracking marks
  • Carbonization
  • Arc erosion
  • Surface contamination
  • Moisture accumulation
  • Loose mounting bolts
  • Abnormal deformation
  • Reduced electrical clearance

Clean the surface using a dry, soft, lint-free cloth. Do not use corrosive solvents, abrasive tools, or metal cleaning equipment.

Stop using the product and replace it immediately if cracks, severe ageing, tracking marks, carbonization, deformation, or other insulation defects are found.

安全注意事项

  • Avoid impact, compression, dropping, and improper stacking during transportation and storage.
  • Do not strike, pry, bend, or force the product into position during installation.
  • Do not drill additional holes, cut the structure, or modify the mounting dimensions.
  • Keep the product away from sharp metal objects and corrosive chemicals.
  • Do not install or remove the product while the equipment is energized.
  • Installation and maintenance must be carried out by qualified electrical personnel.
  • Replace the product immediately if surface cracking, tracking, carbonization, or other abnormal conditions are detected.
  • Always use a replacement with the same model, dimensions, voltage rating, and insulation performance.

Selection and Ordering Information

物品Details
产品型号WB-35Q/140 3AVS
Standard Compatibility1.2-metre 35 kV high-voltage switchgear
Typical Switchgear TypeKYN61-40.5 and compatible cabinet structures
材料APG-cast epoxy resin
定制Customized versions are available for other switchgear dimensions, including 1.4-metre configurations
WB-35Q-140-3AVS 弯板安装支架