15kV Eco-Integrated Node 开关设备 Quick Connectors
产品概述
The 15kV Eco-Integrated Node Switchgear Quick Connectors are dedicated quick-connection devices designed specifically for 10kV/15kV eco-friendly gas (nitrogen/dry air) insulated integrated node switchgear. They enable rapid mating between switchgear and bypass cables/transfer equipment, supporting live-line bypass operations, emergency power supply, and other scenarios where energized switchgear interface connections must be made without de-energization. These connectors are core accessory components for live-line operations on eco-friendly medium-voltage switchgear.
产品特点
电气和绝缘性能
Employing an insulation structure design dedicated to eco-friendly switchgear, compatible with nitrogen/dry air insulating environments, the connectors exhibit excellent insulation performance. They can withstand the rated system voltage of 15kV as well as transient overvoltages, meeting the operational requirements of a maximum working voltage of 17.5kV, with partial discharge level ≤10pC (at 1.5U₀).
内置高纯度铜导电内芯,提供出色的导电性和极低的接触电阻,能够承载250A/630A的额定电流,在长期运行中无发热或氧化现象,满足大电流旁路电源的需求。
集成电场优化结构和绝缘屏蔽罩可均匀分布界面电场,有效抑制局部放电。连接器还提供卓越的密封性能,防止环保气体从开关设备中泄漏,在长期运行中不会发生电气侵蚀或介电击穿的风险,确保稳定可靠的电气和密封性能。
结构与安全特性
标准化接口设计严格遵循环保型一体化节点开关设备行业标准,可与主流15kV环保型气体开关设备专用接口通用互换,兼容性强。
该整体式模块化结构采用无需额外工具的快速锁定连接机制,能够快速连接开关设备和旁路设备,显著缩短带电作业的施工周期。
双功能设计集成了自定位防拔脱锁定和气体密封。在接口完全安装后,该机制会自动锁定,同时有效密封开关设备内的环保气体,防止运行过程中松动、移位和气体泄漏,从而提高系统安全性。
全绝缘防护设计提供了高外绝缘强度,允许在带电运行时直接接触外壳,而不会有触电风险,确保了操作和维护人员的安全。
环境和耐候性
出色的耐候性使其能够适应-40°C至+90°C的宽温度范围。导电内芯和绝缘组件在极端温度下不会出现降解、开裂或变脆,这使得连接器适用于室内和室外环保型开关设备运行。
该连接器具有 IP67 防护等级,防潮、防水、抗污染、抗盐雾,可在潮湿、多尘和含盐的恶劣环境中长期可靠运行,不会受到雨水或冷凝腐蚀的影响。同时兼容氮气/干燥空气绝缘环境,无气体泄漏风险。
导电内芯表面采用锡/银镀层,具有抗老化和防腐蚀性能,可防止氧化和腐蚀;绝缘部件则采用耐环保气体的材料制成。使用寿命超过10年,无需维护,降低了长期运营和维护成本。
机械和兼容性特性
高机械强度,抗冲击和抗振动,使连接器能够承受运输、安装和运行过程中遇到的机械应力,不会发生变形或损坏的风险,适合复杂现场工作环境。
该连接器兼容 10kV/15kV 环保型集成节点开关柜、充氮环网柜、干式空气绝缘紧凑型变电站等设备的专用接口,通用性强,可与主流旁路电缆、过渡电缆、分接装置配套使用。
模块化设计支持反复插拔,维护方便,降低了带电作业的设备投资成本。
技术参数
| 参数类别 | 物品 | 规格 |
| 额定电气参数 | 系统电压 (Un) | 10千伏/15千伏 |
| 额定电压 (Ue) | 15千伏 | |
| 最大工作电压 (Um) | 17.5千伏 | |
| 额定频率 (fn) | 50赫兹/60赫兹 | |
| 工频耐压 | 42kV/5min(干式试验),无击穿,无闪络 | |
| 雷电冲击耐受电压 | 95千伏(峰值),无击穿,无闪络 | |
| 局部放电水平 | ≤10pC (在1.5U₀时) | |
| 额定电流额定值 | 250安培/630安培(可选) | |
| 额定短路耐受电流 | 20kA/2秒,25kA/2秒(可选) | |
| 接触电阻 | ≤20微欧 | |
| 结构和材料参数 | 主体材料 | 镀锡/镀银铜(导电内芯),环保耐气绝缘材料(绝缘组件),不锈钢(锁定机构/法兰) |
| 防护等级 | IP67 | |
| 接口标准 | 兼容15kV环保型箱式变电站专用接口,符合行业标准 | |
| 兼容设备 | 10kV/15kV环保型一体化节点开关设备,氮气/干空气绝缘环网柜,旁路电缆,联络电缆等。 | |
| 密封性能 | 兼容氮气/干燥空气绝缘环境;无气体泄漏风险 | |
| 环境参数 | 适用高度 | ≤2000米(可高海拔定制) |
| 环境温度 | -40°C 至 +90°C(工作温度),-40°C 至 +70°C(储存温度) | |
| 相对湿度 | ≤100%(无冷凝) | |
| 地震烈度 | 八年级 | |
| 适用标准 | GB/T 12706,DL/T 1476 电气安全工具和设备预防性试验规程,DL/T 814 配电自动化终端,GB 3906 3.6kV~40.5kV 交流金属封闭开关设备和控制设备 |
应用范围
适用电压等级:10kV/15kV交流中压配电系统,兼容额定最高工作电压为17.5kV的环保型气体绝缘开关设备。
适用操作场景:
10kV/15kV环保型一体化节点开关柜及充氮/干空气绝缘环网柜的带电检修和改造作业,实现开关柜与旁路电缆的快速对接,建立临时旁路供电回路;
城市配电网带电作业、工业及矿山企业配电系统、新能源(光伏/风电)升压站环保型开关设备;
室内/室外配电室、箱式变电站及类似装置中环保型开关设备上的应急供电和带电维修作业。
功能目的:实现环保型一体化节点开关设备与旁路运行设备之间的绝缘隔离和导电连接,同时保持开关设备内部氮气/干燥空气的密封完整性,为环保型中压配电系统开关设备的带电旁路操作提供安全可靠的连接解决方案。
操作条件
正常运行条件
海拔:≤2000米
环境温度:-40°C 至 +90°C;设备运行温度符合相关标准
相对湿度:≤100%(无冷凝)
环境条件:无腐蚀性气体、易燃易爆介质,无剧烈振动或冲击
安装方式:法兰安装至环保开关柜接口,另一端直接插接至旁路设备接口。水平和垂直安装方向均可;安装空间需满足插拔操作及法兰安装要求。
特殊操作条件(需要定制)
海拔超过2000米
环境温度超出-40°C至+90°C的范围
严重污染、盐碱或化学腐蚀环境
高振动或高冲击工况
非标准接口配置或特殊电流额定值要求
安装与维护
安装要求
安装前,请检查产品外观是否有裂纹、损坏和空洞;确认绝缘部件无损坏。检查导电内芯、锁定机构和密封部件是否无锈蚀和变形,锁定机构是否运行平稳可靠,密封部件是否无老化或劣化。
Clean the inner surface of the eco-friendly switchgear interface and the 连接器 surface, removing grease, dust, and foreign matter, and ensure the interface is dry and clean. Clean the bypass equipment interface surface, removing grease, dust, and foreign matter, and ensure the interface is dry and clean.
在连接器接口外表面均匀涂抹专用的硅脂润滑剂,以防止安装过程中绝缘层和密封件损坏。
通过法兰将连接器固定到环保开关设备接口,并按照规定扭矩拧紧螺栓。将连接器的另一端可靠地连接到旁路设备接口,确保完全就位,然后接合定位防拔锁紧机构。安装后,请检查是否松动或错位。
安装完成后,应进行绝缘电阻测试、工频耐压测试和气体密封性测试;所有测试合格后方可投入运行。
维护要求
定期检查产品外观是否有裂纹、损坏、放电痕迹和污垢堆积;确认与开关设备接口和旁路设备接口的连接牢固,无松动;检查法兰螺栓无松动或腐蚀,密封件无老化或劣化。
定期测试绝缘电阻和接触电阻,同时检查开关柜内部气体压力,以确保性能符合要求并及时发现潜在故障。
清洁产品表面和接口,清除灰尘和污染物;保持绝缘表面干燥清洁,避免油脂和化学物质腐蚀。
如果产品出现开裂、损坏、放电、过热、接触电阻不合格或气体泄漏等异常情况,应立即停止使用并更换;严禁操作有缺陷的设备。
插拔接口操作必须使用专用绝缘操作工具;严禁徒手操作带电接口,所有操作必须严格遵守配电安全规程。
安全注意事项
产品必须由持有中压带电作业资质的合格电气专业人员进行安装、调试和维护;严禁非专业人员操作。
产品必须与同规格的环保型开关设备和旁路操作设备配套使用。严禁与不同电压等级或电流等级的设备混用,否则将导致绝缘失效、安全事故或气体泄漏。
禁止未经授权拆卸或改装产品,否则将导致保修和安全认证失效。严禁使用非专用工具强行安装或拆卸接口和法兰。
安装过程中严禁损坏绝缘表面和密封组件。必须将硅脂润滑剂均匀涂抹,以避免影响绝缘性能和密封效果。法兰安装螺栓必须拧紧至规定扭矩,以防止松动导致端子移动、接口松脱或气体泄漏。
储存期间,产品必须置于干燥、通风、阴凉的环境中,避免阳光直射、高温、潮湿和挤压。严禁与可能损坏绝缘部件和密封部件的尖锐物体接触。
在带电接口进行插拔操作时,必须严格遵守配电安全规程,落实好相应的安全防护措施,严禁非专业人员操作。
型号 designation
| 模型标识符 | 描述 |
|---|---|
| 15千伏 | 适用系统电压等级;额定电压15kV,最高工作电压17.5kV |
| 生态集成节点开关柜快速连接器 | 环保集成节点开关设备快速连接器,用于环保气体绝缘开关设备与旁路操作设备之间的快速对接 |
| 250A/630A | 额定电流等级;分别兼容250A/630A电流负载 |
适用的标准和认证
国际标准:IEC 60840 额定电压高于 30kV(Um=36kV)至 150kV(Um=170kV)的挤塑绝缘电力电缆及其附件——试验方法和要求;IEC 62271-200 高压开关设备和控制设备——第 200 部分:额定电压高于 1kV 及包括 52kV 的交流金属封闭开关设备和控制设备。
国家标准:GB/T 12706 额定电压1kV(Um=1.2kV)至35kV(Um=40.5kV)挤塑绝缘电力电缆及附件;GB 3906 3.6kV~40.5kV交流金属封闭开关设备和控制设备;DL/T 1476 电气安全工具和设备预防性试验规程。
该产品已通过国家高压电器质量监督检验中心型式试验,符合国家电力行业标准。
售后服务
产品保修期:自制造日期起 18 个月,或自调试日期起 12 个月,以先到者为准。
在保修期内,产品出现质量问题可免费维修或更换。
提供技术支持、安装指导及定制化服务(特殊规格和特殊工况适应)。
文档通知
本手册中的技术参数基于标准运行条件。特殊运行条件需根据实际需求进行定制。产品技术协议和型式试验证书为最终权威参考。
附录:产品外形图