TG2-10Q/182(152×152) 套管

The TG2-10Q/182 (152×152) is an indoor epoxy resin high-voltage wall bushing manufactured as an integrated cast structure using the APG pressure gelation process.

分享至:

产品概述

TG2-10Q/182 (152×152) 衬套 是一种室内环氧树脂高压穿墙套管,采用APG压力凝胶工艺整体浇注成型。

它适用于额定电压为10千伏及以下的交流三相电力系统。套管允许导电母线或电缆穿过接地体。 switchgear 隔断、墙壁及类似结构,同时提供电气绝缘、机械支撑和导体连接。

It is widely used in withdrawable switchgear, ring main units, and other complete power distribution equipment.

模型描述

型号代码描述
TG2Second-generation wall bushing series for withdrawable switchgear
10QRated voltage of 10 kV; Q indicates an indoor type
182Parameter related to the creepage distance or structural height of the bushing body
152×152Square mounting flange dimensions, 152 × 152 mm

技术规格

电气参数

参数规格
额定电压10 kV, suitable for systems rated from 10 to 35 kV
额定频率50/60 Hz, suitable for systems from 15 to 60 Hz
额定绝缘水平12/42/75 kV, rated voltage/power-frequency withstand voltage/lightning impulse withstand voltage
工频耐压42 kV for 1 minute under dry conditions
雷电冲击耐受电压75 kV peak
局部放电≤5 pC at rated voltage
爬电距离≥182 mm

结构和尺寸参数

参数规格
安装法兰尺寸152 × 152 mm, square
总高度260 mm
Inner Opening DiameterSuitable for standard busbars used in 10 kV withdrawable switchgear, typically approximately Ø100 mm
棚屋结构Double shed groups at the upper and lower ends to improve surface insulation
材料Glass-fibre-reinforced epoxy resin
ColourStandard epoxy resin red; customizable

机械和环境参数

参数规格
弯曲强度≥120 MPa
抗压强度≥150 MPa
工作温度范围-40°C to +120°C for long-term operation
阻燃等级UL94 V-0
Moisture and Pollution ResistanceExcellent, suitable for humid and dusty indoor environments

产品特点

Excellent Insulation Performance

The bushing is integrally cast using the APG process, producing a dense structure without bubbles or visible defects.

It provides high dielectric strength and extremely low partial discharge, helping reduce the risk of surface flashover and maintain stable insulation performance.

高机械强度

The glass-fibre-reinforced epoxy resin structure provides excellent bending, compression, and impact resistance.

It can withstand busbar installation stress and the electrodynamic forces generated under short-circuit conditions.

强大的环境适应性

The product provides reliable resistance to moisture, contamination, high temperatures, and low temperatures.

No special maintenance is normally required. Periodic cleaning of the insulating surface is sufficient under standard operating conditions.

Optimized Structural Design

The double-shed structure increases the creepage distance and improves surface insulation performance.

The square mounting flange is compatible with standard switchgear openings, providing convenient installation and reliable sealing.

Safe and Environmentally Responsible

The product complies with RoHS environmental requirements and contains no toxic or hazardous substances.

Under standard operating conditions, its expected service life is at least 30 years.

应用

Applicable Equipment

The product is suitable for indoor power distribution equipment rated at 10 kV and below, including:

  • KYN28 withdrawable switchgear
  • 环网柜
  • Box-type substations
  • Switchgear partitions
  • Power distribution room walls
  • Other indoor medium-voltage electrical assemblies

主要功能

  • Electrical insulation where conductive busbars or cables pass through grounded partitions or walls
  • Mechanical support and fixation of busbars
  • Transitional busbar connections inside or between switchgear cabinets
  • Insulation separation between live conductors and grounded structures
  • Conductor support in complete power distribution equipment

适用系统

The bushing is suitable for three-phase AC power systems with a rated frequency of 50/60 Hz, including:

  • Power stations
  • Substations
  • Industrial power distribution rooms
  • Commercial and infrastructure power distribution systems

操作条件

正常运行条件

  • Ambient temperature: -5°C to +40°C
  • Daily average ambient temperature: no more than +35°C
  • Installation altitude: no more than 1,000 m
  • Daily average relative humidity: no more than 95%
  • Monthly average relative humidity: no more than 90%
  • Condensation is not permitted
  • Indoor installation only
  • The environment should be free from severe pollution
  • Corrosive gases are not permitted
  • Flammable or explosive substances are not permitted
  • Severe vibration and mechanical impact should be avoided

Special Operating Conditions

Customized products are required under the following conditions:

  • Installation altitude above 1,000 m, with insulation correction according to GB/T 11022
  • Ambient temperatures outside the range of -5°C to +40°C
  • Severe pollution or salt-spray environments
  • Chemically corrosive environments
  • Applications involving severe vibration or mechanical impact

安装与维护

安装要求

  1. Pre-installation inspection: Confirm that the bushing is free from cracks, damage, bubbles, and other visible defects. Check that the flange is flat and that the dimensions meet the installation requirements.
  2. Installation method: Insert the bushing through the switchgear partition or wall and secure the flange with bolts. Ensure that the sealing gasket, where provided, is correctly installed to prevent air movement between switchgear compartments.
  3. Busbar installation: Pass the busbar through the inner opening. Ensure that the busbar does not contact the inner wall or apply mechanical stress to the bushing. Maintain sufficient and even insulation clearance.
  4. Grounding requirements: The mounting flange must be reliably connected to the switchgear enclosure or grounded wall structure. The grounding resistance must comply with the applicable requirements.

维护要求

  1. Routine maintenance: No special maintenance is normally required. Clean dust and contamination from the bushing surface every 6 to 12 months to keep the insulating surface clean and dry.
  2. Periodic testing: During scheduled switchgear maintenance, conduct insulation resistance and power-frequency withstand voltage tests to confirm that the insulation performance remains acceptable.
  3. Replacement conditions: Replace the bushing immediately if cracks, mechanical damage, severe contamination, or reduced insulation performance are found.

适用标准

  • GB/T 12944.1, High-Voltage Wall Bushings—Part 1: Porcelain and Glass-Fibre Bushings
  • GB/T 11022, Common Specifications for High-Voltage Switchgear and Controlgear Standards
  • IEC 60137, Insulated Bushings for Alternating Voltages Above 1,000 V
  • JB/T 10686, Indoor Epoxy Resin Cast Wall Bushings for 1 kV to 35 kV Systems

注意事项

  1. This product is intended for indoor use only and must not be installed directly in exposed outdoor environments.
  2. Avoid severe impact, dropping, and rough handling during installation and transportation to prevent cracking.
  3. Do not drill, cut, or otherwise machine the bushing surface, as this may damage the insulating structure.
  4. For high-altitude, high-temperature, corrosive, or other special operating conditions, inform the manufacturer in advance so that a customized product can be supplied.
  5. Store the product in a dry, ventilated environment free from corrosive gases and protect it from moisture.
TG2-10Q-182152×152-衬套